Owners and operators shall apply corrosion protection to all steel tanks and tank systems except as otherwise provided in subpart 5.
The floor of an existing steel aboveground storage tank must be protected from external corrosion using one or more of the following methods:
the tank is elevated so that the underside of the tank's floor is not in contact with any surface other than the supports;
the tank rests on a continuous concrete slab that is designed to prevent water from accumulating under the tank floor;
An existing steel line must be protected from external corrosion using one or more of the following methods:
Cathodic protection of existing steel tanks and lines must be designed by a corrosion expert in accordance with American Petroleum Institute Standards 651 and 1632, as applicable.
A secondary containment area for tanks or tank systems which complies with the requirements of part 7151.5400, subparts 1, 2, 3, items B to I, and 4, is excluded from the requirements of this part.
Owners and operators shall comply with this part effective November 1, 2003.