The table in this part governs emission limitations for Class A and C waste combustor units. For acid gas limitations, either the applicable percent reduction or the parts per million by volume emission limitation, whichever is less stringent, is the emission limitation for the waste combustor.
Class C | Class A | ||
Particulate Matter | |||
Front-half | 0.012 gr/dscf | ||
Total | 0.020 gr/dscf | 0.020 gr/dscf | |
PCDD/PCDF | |||
Total | 500 ng/dscm | 30 ng/dscm | |
Acid Gases: | |||
Hydrogen chloride | NA | 95% control or 29 ppm | |
Sulfur dioxide | NA | 75% control or 29 ppm | |
Carbon Monoxide | |||
Modular starved air | 50 ppm | 50 ppm | |
Modular excess air | 50 ppm | 50 ppm | |
Mass burn waterwall | 100 ppm | 100 ppm | |
Mass burn refractory | 100 ppm | 100 ppm | |
Mass burn rotary refractory | 100 ppm | 100 ppm | |
Mass burn rotary waterwall | 250 ppm | 250 ppm | |
Bubbling fluidized bed | 100 ppm | 100 ppm | |
Circulating fluidized bed | 100 ppm | 100 ppm | |
Pulverized coal/refuse-derived fuel mixed fuel-fired combustor | NA | 150 ppm | |
Spreader stoker coal/refuse-derived fuel mixed fuel-fired combustor | NA | 200 ppm | |
RDF stoker | 150 ppm | 200 ppm | |
Opacity | 10% | 10% | |
Mercury (short-term) | |||
Modular with ESP | 1,000 µg/dscm | NA | |
Mass burn | 1,000 µg/dscm | NA | |
Modular, mass burn, or fluidized bed with wet or dry scrubber | 100 µg/dscm or 85% removal | NA | |
For all waste combustors except those combusting RDF in spreader stokers | NA | 80 µg/dscm or 85% removal | |
Waste combustor units combusting RDF in spreader stokers (90-day test interval) | NA | 50 µg/dscm or 85% removal | |
Mercury (long-term) | |||
Modular with ESP | 600 µg/dscm | NA | |
Mass burn | 600 µg/dscm | ||
Modular, mass burn, or fluidized bed with wet or dry scrubber | 60 µg/dscm or 85% removal | NA | |
For all waste combustors except those combusting RDF in spreader stokers | NA | 60 µg/dscm or 85% removal | |
Waste combustor units combusting RDF in spreader stokers (90-day test interval) | NA | 30 µg/dscm or 85% removal | |
Waste combustor units combusting RDF in spreader stokers (12-month test interval) | NA | 30 µg/dscm or 85% removal | |
Cadmium | NA | 40 µg/dscm | |
Lead | NA | 440 µg/dscm |
MS s 116.07
18 SR 2584; 22 SR 1975
February 25, 2008
Official Publication of the State of Minnesota
Revisor of Statutes