A well vent must:
be constructed of materials complying with parts 4725.2250 to 4725.2650, or 4725.5150, subpart 1;
have watertight joints and terminate at least five feet above the regional flood level unless provided with a watertight seal as specified in part 4725.4350, subpart 2;
terminate a minimum of 12 inches above the established ground surface or the floor of a building as specified in part 4725.2175, except that a vent for a community public water-supply well must terminate a minimum of 18 inches above the established ground surface and the floor of a building as specified in part 4725.2175;
be screened with a noncorrosive mesh screen having openings of 1/16 inch or less and pointed downward; and
A screened vent incorporated into the underside of a well cap or cover may be used.