The water recirculation system must clarify and disinfect the pool volume of water in six hours or less.
The water recirculation system of a wading pool or a special purpose pool must recirculate a water volume equal to the pool volume in two hours or less.
The recirculation system in a spa pool must recirculate a water volume equal to the pool volume in 30 minutes or less, except that a minimum rate of 35 gallons per minute is required.
The recirculation system of a dedicated plunge pool must recirculate a water volume equal to the total volume of the pool in one hour or less.
19 SR 1419; 19 SR 1637
May 11, 2009
Official Publication of the State of Minnesota
Revisor of Statutes