The size of the building storm drain or any of its horizontal branches having a slope of one-half inch or less per foot, shall be based upon the maximum projected roof or paved area to be handled according to subpart 4.
Vertical leaders shall be sized on the maximum projected roof area, according to subpart 5.
Storm drain piping shall not reduce in size in the direction of flow, including changes in direction from horizontal to vertical.
Diameter of Drain | Maximum Projected Roof Area for Drains of Various Slopes | ||
Inches | 1/8 in. Slope | 1/4 in. Slope | 1/2 in. Slope |
Square Feet | Square Feet | Square Feet | |
3 | 822 | 1,160 | 1,644 |
4 | 1,880 | 2,650 | 3,760 |
5 | 3,340 | 4,720 | 6,680 |
6 | 5,350 | 7,550 | 10,700 |
8 | 11,500 | 16,300 | 23,000 |
10 | 20,700 | 29,200 | 41,400 |
12 | 33,300 | 47,000 | 66,600 |
15 | 59,500 | 84,000 | 119,000 |
Use a rate of rainfall of four inches per hour for sizes not listed in this table.
Size of Leader or Conductor Inches |
Maximum Projected Roof Area Square Feet |
2 | 720 |
2-1/2 | 1,300 |
3 | 2,200 |
4 | 4,600 |
5 | 8,650 |
6 | 13,500 |
8 | 29,000 |
Use a rate of rainfall of four inches per hour for sizes not listed in this table.
The equivalent diameter of square or rectangular leader may be taken as the diameter of that circle which may be inscribed within the cross-sectional area of the leader.
If there is a continuous or semicontinuous discharge into the building storm drain or building storm sewer, as from a pump, ejector, or similar device, each gallon per minute of the discharge must be computed as being equivalent to 24 square feet of roof area, based upon a four-inch rainfall.