Horizontal drainage piping shall be installed in uniform alignment at uniform slopes in accordance with the following requirements and in no case at a slope which will produce a computed velocity of less than two feet per second, unless otherwise permitted by the administrative authority, based on hydraulic analysis of the piping system.
Size of Piping | Minimum Slope |
Less than 3 inches | 1/4 inch per foot |
3 inches to 6 inches | 1/8 inch per foot |
8 inches and over | 1/16 inch per foot |