Pipe sizes for gravity drains shall be determined from subparts 2 and 3 on the basis of drainage load computed from part 4715.2300, subparts 2 and 3.
Building Sewer*****, Building Drain and
Building Drain Branches - from Stacks**** _ |
|||||
Diameter of Drain |
Horizontal Fixture Branch*- |
Slope
_ |
|||
(inches) | (f.u.) | 1/16 in/ft. (f.u.) |
1/8 in/ft. (f.u.) |
1/4 in/ft. (f.u.) |
1/2 in/ft. (f.u.) |
1-1/4 | 1 | ||||
1-1/2 | 3 | ||||
2 | 6 | 21 | 26 | ||
2-1/2 | 12 | 24 | 31 | ||
3** | 32*** | 36*** | 42*** | 50*** | |
4 | 160 | 180 | 216 | 250 | |
5 | 360 | 390 | 480 | 575 | |
6 | 620 | 700 | 840 | 1,000 | |
8 | -- | 1,400 | 1,600 | 1,920 | 2,300 |
10 | -- | 2,500 | 2,900 | 3,500 | 4,200 |
12 | -- | 3,900 | 4,600 | 5,600 | 6,700 |
15 | -- | 7,000 | 8,300 | 10,000 | 12,000 |
*Includes Horizontal Branches of the Building Drain.
**No water closet shall discharge into a drain less than 3 inches.
***Not over 2 Water Closets.
****Every building drain that receives the discharge of (3) or more water closets, shall not be less than 4 inches in diameter.
*****No building sewer shall be less than 4 inches in diameter.
Diameter of Stack | Stacks of not more than 3 stories or Branch Intervals | Stacks of more than 3 stories or Branch Intervals | Total at One Story or Branch Interval |
1-1/4* | 2 | 2 | 1 |
1-1/2* | 4 | 4 | 2 |
2* | 9 | 18 | 6 |
2-1/2* | 20 | 42 | 9 |
3 | 36*** | 72*** | 24** |
4 | 240 | 500 | 90 |
5 | 540 | 1,100 | 200 |
6 | 960 | 1,900 | 350 |
8 | --- | 3,600 | 600 |
10 | --- | 5,600 | 1,000 |
12 | --- | 8,400 | 1,500 |
*No water closets permitted.
**Not over 2 water closets permitted.
***Not over 6 water closets permitted, and not over 6 branch intervals on a 3 inch soil stack.
MS s 16B.59; 16B.61; 16B.64; 326.37 to 326.45; 326B.101; 326B.106; 326B.13; 326B.43 to 326B.49
28 SR 146; L 2007 c 140 art 4 s 61; art 6 s 15; art 13 s 4; 33 SR 2042