4714.0717 SIZE OF BUILDING SEWERS.
UPC section 717, Table 717.1, is amended to read as follows:
| TABLE 717.1 | |||
| Maximum/Minimum Fixture Unit Loading on Building Sewer Piping | |||
| Size of Pipe (inches) |
SLOPE (inches per foot) |
||
| 1/16 | 1/8 | 1/4 | |
| 6 and smaller | (As specified in Table 703.2/No minimum loading) | ||
| 8 | 1950/1500 | 2800/625 | 3900/275 |
| 10 | 3400/1600 | 4900/675 | 6800/300 |
| 12 | 5600/1700 | 8000/725 | 11 200/325 |
For SI units: 1 inch = 25 mm, 1 inch per foot = 83.3 mm/m