UPC section 608.5 is amended to read as follows:
608.5 Discharge Piping. The discharge piping serving a temperature relief valve, pressure relief valve, or combination of both shall have no valves, obstructions, or means of isolation and shall:
(1) be equal to the size of the valve outlet and shall discharge full size to the flood level of the area receiving the discharge and pointing down;
(2) consist of materials rated at not less than the operating temperature of the system and shall be approved for such use or comply with ASME A112.4.1;
(3) discharge independently by gravity through an air gap to a safe place of disposal or within 18 inches of the floor. Relief valve drains shall not terminate in a building's crawl space;
(4) discharge in such a manner that does not cause personal injury or structural damage;
(5) not consist of any part that may be trapped or subject to freezing;
(6) not consist of a threaded terminal end of the pipe; and
(7) not discharge from a relief valve into a water heater pan.