4714.0507 OTHER WATER HEATER INSTALLATION REQUIREMENTS.
§
Subpart 1.
Sections 507.6 to 507.11 and 507.14 to 507.23.
UPC sections 507.6 to 507.11 and 507.14 to 507.23 are deleted in their entirety.
§
Subp. 2.
Section 507.5.
UPC section 507.5 is amended to read as follows:
507.5 Relief Valve Discharge. Discharge from a relief valve into a water heater pan shall be prohibited. Discharge relief valves shall terminate to a safe place of disposal or within 18 inches of the floor.