Table 313.3 is amended to read as follows:
TABLE 313.3 | |||
HANGERS AND SUPPORTS | |||
MATERIALS | TYPES OF JOINTS | HORIZONTAL | VERTICAL |
Cast | Lead and Oakum | 5 feet, except 10 feet where 10 foot lengths are installed1,2,3 | Base and each floor, not to exceed 15 feet |
Compression Gasket | Every other joint, unless over 4 feet then support each joint1,2,3 | Base and each floor, not to exceed 15 feet | |
Cast-Iron Hubless | Shielded Coupling | Every other joint, unless over 4 feet then support each joint1,2,3,4 | Base and each floor, not to exceed 15 feet |
Copper & Copper Alloys | Soldered, Brazed, Threaded, or Mechanical | 1-1/2 inches and smaller, 6 feet; 2 inches and larger, 10 feet | Each floor, not to exceed 10 feet5 |
Steel Pipe for Water or DWV | Threaded or Welded | 3/4 inch and smaller, 10 feet; 1 inch and larger, 12 feet | Every other floor, not to exceed 25 feet5 |
Steel Pipe for Gas | Threaded or Welded | 1/2 inch, 6 feet; 3/4 inch and 1 inch, 8 feet; 1-1/4 inches and larger, 10 feet | 1/2 inch, 6 feet; 3/4 inch and 1 inch, 8 feet; 1-1/4 inches every floor level |
Schedule 40 PVC and ABS DWV | Solvent Cemented | All sizes, 4 feet; allow for expansion every 30 feet3,6 | Base and each floor; provide mid-story guides; provide for expansion every 30 feet6 |
CPVC | Solvent Cemented | 1 inch and smaller, 3 feet; 1-1/4 inches and larger, 4 feet | Base and each floor; provide mid-story guides |
CPVC-AL-CPVC | Solvent Cemented | 1/2 inch, 5 feet; 3/4 inch, 65 inches; 1 inch, 6 feet | Base and each floor; provide mid-story guides |
Lead | Wiped or Burned | Continuous Support | Not to exceed 4 feet |
Steel | Mechanical | In accordance with standards acceptable to the Authority Having Jurisdiction | |
PEX | Cold Expansion, Insert, and Compression | 1 inch and smaller, 32 inches; 1-1/4 inches and larger, 4 feet | Base and each floor; provide mid-story guides |
PEX-AL-PEX | Metal Insert and Metal Compression | 1/2 inch; 3/4 inch; 1 inch All sizes 98 inches |
Base and each floor; provide mid-story guides |
PE-AL-PE | Metal Insert and Metal Compression | 1/2 inch; 3/4 inch; 1 inch All sizes 98 inches |
Base and each floor; provide mid-story guides |
PE-RT | Insert and Compression | 1 inch and smaller, 32 inches; 1-1/4 inches and larger, 4 feet | Base and each floor; provide mid-story guides |
Polypropylene (PP) | Fusion Weld (socket, butt, saddle, electrofusion), Threaded (metal threads only), or Mechanical | 1 inch and smaller, 32 inches; 1-1/4 inches and larger, 4 feet | Base and each floor; provide mid-story guides |
For SI units: 1 inch = 25.4 mm, 1 foot = 304.8 mm
Notes:
1 Support adjacent to joint, not to exceed 18 inches (457 mm).
2 Brace not to exceed 40-foot (12,192 mm) intervals to prevent horizontal movement.
3 Support at each horizontal branch connection.
4 Hangers shall not be placed on the coupling.
5 Vertical water lines shall be permitted to be supported in accordance with recognized engineering principles with regard to expansions and contraction, where first approved by the Authority Having Jurisdiction.
6 For expansion joints, see Table 313.3.1.
Table 313.3.1 is added to read as follows:
TABLE 313.3.1 |
|||
Schedule 40 PVC and ABS DWV and Storm Pipe Expansion Table |
|||
Inside the building thermal envelope |
|||
Length of Run (ft.) |
|||
101 |
201 |
30 |
|
Pipe Size |
Expansion joint length (in.) = L |
||
1.5" |
20 |
28 |
34 |
2" |
22 |
31 |
38 |
3" |
27 |
38 |
46 |
4" |
30 |
43 |
52 |
6" |
37 |
52 |
63 |
8" |
42 |
59 |
72 |
10" |
47 |
66 |
80 |
12" |
51 |
72 |
88 |
Outside the building thermal envelope |
|||
Length of Run (ft.) |
|||
101 |
201 |
30 |
|
Pipe Size |
Expansion joint length (in.) = L |
||
1.5" |
26 |
36 |
44 |
2" |
29 |
41 |
50 |
3" |
35 |
49 |
60 |
4" |
40 |
56 |
68 |
6" |
48 |
68 |
83 |
8" |
55 |
77 |
94 |
10" |
61 |
86 |
105 |
12" |
66 |
94 |
114 |
1 Multiple offsets shall be allowed to provide expansion for each 30-foot developed length of run.