1323.1132 SECTION 11.3.2, HVAC SYSTEMS.
ASHRAE Standard 90.1, Section 11, Table 11.3.2C, is amended to read:
TABLE 11.3.2C Water Chiller Types.
| Individual Chiller Plant Capacity | Electric Chiller Type | Fossil Fuel Chiller Type |
| ≤100 tons | Reciprocating | Double-effect absorption direct/indirect fired or Single-effect absorption using waste heat |
| >100 tons, <300 tons | Screw | Double-effect absorption, direct fired |
| ≥300 tons | Centrifugal | Double-effect absorption, direct fired |