ASHRAE Standard 90.1, Section 7, Table 7.8, is amended to read:
TABLE 7.8 Performance Requirements for Water Heating Equipment
Equipment Type | Size Category (Input) | Subcategory or Rating Condition | Performance Requireda |
Electric Water Heaters | ≤12 kW | Resistance ≥20 gal | 0.97-0.00132V EF |
>12 kW | Resistance ≥20 gal | 20+35 √V SL, Btu/h | |
≤24 Amps and ≤250 Volts | Heat Pump | 0.97-0.00132V EF | |
Gas Storage Water Heaters | ≤75,000 Btu/h | ≥20 gal | 0.67-0.0019V EF |
>75,000 Btu/h | <4,000(Btu/h)/gal | 80% Et(Q/800+110 √V) SL, Btu/h | |
Gas Instantaneous Water Heaters | >50,000 Btu/h and <200,000 Btu/h | ≥4,000(Btu/h)/gal and <2 gal | 0.67-0.0019V EF |
≥200,000 Btu/hc | ≥4,000(Btu/h)/gal and <10 gal | 80% Et | |
≥200,000 Btu/h | ≥4,000(Btu/h)/gal and ≥10 gal | 80% Et(Q/800+110 √V) SL, Btu/h | |
Oil Storage Water Heaters | ≤105,000 Btu/h | ≥20 gal | 0.59-0.0019V EF |
>105,000 Btu/h | <4,000(Btu/h)/gal | 78% Et(Q/800+110 √V) SL, Btu/h | |
Oil Instantaneous Water Heaters | ≤210,000 Btu/h | ≥4,000(Btu/h)/gal and <2 gal | 0.59-0.0019V EF |
>210,000 Btu/h | ≥4,000(Btu/h)/gal and <10 gal | 80% Et | |
>210,000 Btu/h | ≥4,000(Btu/h)/gal and ≥10 gal | 78% Et(Q/800+110 √V) SL, Btu/h | |
Hot Water Supply Boilers, Gas and Oil | ≥300,000 Btu/h and <12,500,000 Btu/h | ≥4,000(Btu/h)/gal and <10 gal | 80% Et |
Hot Water Supply Boilers, Gas | ≥4,000(Btu/h)/gal and ≥10 gal | 80% Et(Q/800+110 √V) SL, Btu/h | |
Hot Water Supply Boilers, Oil | ≥4,000(Btu/h)/gal and ≥10 gal | 78% Et(Q/800+110 √V) SL, Btu/h | |
Pool Heaters Oil and Gas | All | 78% Et | |
Heat Pump Pool Heaters | All | 4.0 COP | |
Unfired Storage Tanks | All | R-12.5 |
aEnergy factor (EF) and thermal efficiency (Et) are minimum requirements, while standby loss (SL) is maximum Btu/h based on a 70° F temperature difference between stored water and ambient requirements. In the EF equation, V is the rated volume in gallons. In the SL equation, V is the rated volume in gallons and Q is the nameplate input rate in Btu/h.
bInstantaneous water heaters with input rates below 200,000 Btu/h must comply with these requirements if the water heater is designed to heat water to temperatures 180° F or higher.