ASHRAE Standard 90.1, Table 6.8.1C, is amended to read:
TABLE 6.8.1C Water Chilling Packages - Minimum Efficiency Requirements
Equipment Type | Size Category | Subcategory or Rating Condition | Minimum Efficienciesa | Test Procedureb |
Air Cooled, with Condenser, Electrically Operated | All Capacities | 2.80 COP 3.05 IPLV | ARI 550/590 | |
Air Cooled, without Condenser, Electrically Operated | All Capacities | 3.10 COP 3.45 IPLV | ||
Water Cooled, Electrically Operated, Positive Displacement (Reciprocating) | All Capacities | 4.20 COP 5.05 IPLV | ARI 550/590 | |
Water Cooled, Electrically Operated, Positive Displacement (Rotary Screw and Scroll) | <150 tons | 4.45 COP 5.20 IPLV | ARI 550/590 | |
≥150 tons and <300 tons | 4.90 COP 5.60 IPLV | |||
≥300 tons | 5.50 COP 6.15 IPLV | |||
Water Cooled, Electrically Operated, Centrifugal | <150 tons | 5.00 COP 5.25 IPLV | ARI 550/590 | |
≥150 tons and <300 tons | 5.55 COP 5.90 IPLV | |||
≥300 tons | 6.10 COP 6.40 IPLV | |||
Air-Cooled Absorption Single Effectc | All Capacities | 0.60 COP | ARI 560 | |
Water-Cooled Absorption Single Effectc | All Capacities | 0.70 COP | ||
Absorption Double Effect, Indirect-Fired | All Capacities | 1.00 COP 1.05 IPLV | ||
Absorption Double Effect, Direct-Fired | All Capacities | 1.00 COP 1.00 IPLV |
aThe chiller equipment requirements do not apply for chillers used in low-temperature applications where the design leaving fluid temperature is <40° F.
bSection 12 contains a complete specification of the referenced test procedure, including the reference year version of the test procedure.
cSee Section 6.9.1.