GREB Section 413.2.3, the Exceptions are amended to read as follows:
Exceptions:
1. If the existing load is less than 10 kva as computed in accordance with the Minnesota Electrical Code, an existing 60 ampere three-wire service shall be permitted.
2. 30-ampere and larger two- or three-wire feeders supplying dwelling units shall be permitted where the feeders are adequate for the load served as computed in the Minnesota Electrical Code.
GREB Section 413.2.4.3 is amended as follows:
413.2.4.3 Laundry areas shall have a minimum of one grounded-type outlet or a receptacle outlet protected with a ground-fault circuit-interrupter located near each piece of laundry equipment and at least one lighting outlet.
GREB Section 413.2.4.5 is amended as follows:
413.2.4.5 At least one lighting outlet shall be provided in every kitchen, toilet room, bathroom, hallway, stairway, attached garage, and detached garage with electric power.
GREB Section 413.2.4 is amended by adding the following subsection:
413.2.4.8 Each toilet room and bathroom shall have a receptacle outlet provided with ground-fault circuit-interrupter protection.
27 SR 1479; L 2007 c 140 art 4 s 61; art 13 s 4