1311.0405 SECTION 405, FIRE ESCAPES.
Section 405.4 Dimensions. IEBC section 405.4 is amended to read as follows:
405.4 Dimensions. Existing and replacement fire escape stairs shall meet the minimum width, capacity, riser height, and tread depth as specified in Table 405.4.
| TABLE 405.4 DIMENSIONS FOR EXISTING AND REPLACEMENT FIRE ESCAPE STAIRS |
||
| Feature | Serving More Than 10 Occupants |
Serving 10 or Fewer Occupants |
| Minimum Width | 22 inches | 18 inches |
| Maximum Riser Height | 9 inches | 12 inches |
| Minimum Tread Depth | 9 inches | 6 inches |