Section 405.4 Dimensions. IEBC section 405.4 is amended to read as follows:
405.4 Dimensions. Existing and replacement fire escape stairs shall meet the minimum width, capacity, riser height, and tread depth as specified in Table 405.4.
TABLE 405.4 DIMENSIONS FOR EXISTING AND REPLACEMENT FIRE ESCAPE STAIRS |
||
Feature | Serving More Than 10 Occupants |
Serving 10 or Fewer Occupants |
Minimum Width | 22 inches | 18 inches |
Maximum Riser Height | 9 inches | 12 inches |
Minimum Tread Depth | 9 inches | 6 inches |
27 SR 1479; L 2007 c 140 art 4 s 61; art 13 s 4; 39 SR 95
January 26, 2015
Official Publication of the State of Minnesota
Revisor of Statutes