IRC Section R302.1 is amended to read as follows:
R302.1 Exterior walls. Construction, projections, openings, and penetrations of exterior walls of dwellings and accessory buildings shall comply with Table 302.1. These provisions shall not apply to walls, projections, openings, or penetrations in walls that are perpendicular to the line used to determine the fire separation distance. Projections beyond the exterior shall not extend more than 12 inches (305 mm) into areas where openings are prohibited.
Exceptions:
1. Detached garages accessory to a dwelling located within 2 feet (610 mm) of a lot line are permitted to have eave projections not exceeding 4 inches (103 mm).
2. Foundation vents installed in compliance with this code are permitted.
TABLE R302.1
EXTERIOR WALLS
EXTERIOR WALL ELEMENT | MINIMUM FIRE-RESISTANCE RATING | MINIMUM FIRE SEPARATION DISTANCE | |
Walls | |||
(Fire-resistance rated) | 1 hour with exposure from both sides | 0 feet | |
(Not fire-resistance rated) | 0 hours | 5 feet | |
Projections | |||
(Fire-resistance rated) | 1 hour on the undersidea | 4 feet | |
(Not fire-resistance rated) | 0 hours | 5 feet | |
Openings | |||
Not allowed | N/A | <3 feet | |
25 % Maximum of Wall Area | 0 hours | 3 feet | |
Unlimited | 0 hours | 5 feet | |
Penetrations | |||
All | Comply with Section R317.3 | <5 feet | |
None required | 5 feet |
N/A= Not Applicable
a 1 hour on the underside equates to one layer of 5/8" type X gypsum sheathing. Openings are not allowed.
32 SR 12; L 2007 c 140 art 4 s 61; art 13 s 4