IBC Table 2308.6.1, Wall Bracing Requirements, is amended to read as follows:
TABLE 2308.6.1a
WALL BRACING REQUIREMENTS
Design Category (Wind Speed) | Story Condition (see Section 2308.2) | Maximum Spacing of Braced Wall Lines | Braced Panel Location, Spacing (o.c.) and Minimum Percentage (x) |
Maximum Distance of Braced Wall Panels from Each End of Braced Wall Line | ||||
Bracing Methodb | ||||||||
LIB | DWB, WSP | SFB, PBS, PCP, HPS, GB c,d |
||||||
See Section 1609.3 |
■ | ■ □ |
■ □ □ |
35'-0" | Each end and < 25'-0" o.c. | Each end and < 25'-0" o.c. | Each end and < 25'-0" o.c. | 12'-6" |
□ ■ |
□ ■ □ |
35'-0" | Each end and < 25'-0" o.c. | Each end and < 25'-0" o.c. | Each end and < 25'-0" o.c. | 12'-6" | ||
□ □ ■ |
35'-0" | NP | Each end and < 25'-0" o.c. | Each end and < 25'-0" o.c. | 12'-6" |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm
NP = Not permitted
a This table specifies minimum requirements for braced wall panels along interior or exterior braced wall lines.
b See section 2308.6.3 for full description of bracing methods.
c For method GB, gypsum wallboard applied to framing supports that are spaced at 16 inches on center.
d The required lengths shall be doubled for gypsum board applied to only one face of a braced wall panel.
32 SR 7; L 2007 c 140 art 4 s 61; art 13 s 4; L 2008 c 337 s 64; 44 SR 609