1305.1008 SECTION 1008, DOORS, GATES, AND TURNSTILES.

Subpart 1.

[Repealed, 32 SR 7]

Subp. 2.

[Repealed, 32 SR 7]

Subp. 3.

[Repealed, 32 SR 7]

Subp. 4.

IBC Section 1008.1.3.

IBC Section 1008.1.3 is amended by adding a subsection to read as follows:

1008.1.3.6 Special egress control devices. Where the clinical needs of the patients require specialized security measures for their safety, door locking arrangements are permitted in Group I-1 occupancies (this includes use groups as described in Group I-1 occupancies that are identified as either Group R-3 or Group R-4 occupancies because of occupant load) and Group I-2 occupancies provided that:

1. keys or devices that function like keys are carried by staff at all times;

2. in at least one egress path, not more than one such arrangement is located;

3. the building or fire area is protected by an approved automatic sprinkler system in accordance with Section 903.3.1.1 (NFPA 13) and an approved fire alarm system having smoke detection, installed throughout the exit corridor system and areas open to the exit corridor;

4. locking devices automatically unlock upon activation of any of the following:

a. automatic sprinkler system;

b. automatic smoke detection system;

c. automatic fire alarm system; or

d. loss of electrical power;

5. locking devices can be remotely unlocked from an approved location within the secured area;

6. there is no public assembly space within the secured area;

7. 24-hour patient supervision is provided within the secured area;

8. relocking of the locking device is by manual means from an approved location within the secured area;

9. locking devices are designed to fail in the open position;

10. special egress control devices are not permitted in buildings of type III-B or V-B construction, and shall not exceed one story in height when in type III-A, IV-HT, or type V-A construction;

11. floor levels within the building or portion of the building with the special egress control devices shall be divided into at least two compartments by smoke barriers meeting the requirements of Section 709; and

12. substitution of the automatic sprinkler system for one-hour fire-resistance-rated construction (pursuant to Table 601, footnote d) is permitted.

Subp. 5.

IBC Section 1008.1.4.

IBC Section 1008.1.4 is amended by modifying exception 5 to read as follows:

Exceptions:

5. Exterior decks, patios, or balconies that are part of Type B dwelling units, have impervious surfaces, and that are not more than two inches (50 mm) below the finished floor level of the adjacent interior space of the dwelling unit.

Subp. 6.

IBC Section 1008.1.8.3.

IBC Section 1008.1.8.3 is amended to read as follows:

1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists:

1. Places of detention or restraint.

2. In buildings in occupancy Group A having an occupant load of 300 or less, in buildings in occupancy Groups B, F, M, and S, and in churches, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided:

2.1. The locking device is readily distinguishable as locked.

2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background.

2.3. The use of the key-operated locking device is revokable by the building official for due cause.

3. Where egress doors are used in pairs, approved automatic flush bolts shall be permitted to be used, provided that the door leaf having the automatic flush bolts has no doorknob or surface-mounted hardware.

4. Doors from individual dwelling or sleeping units of Group R occupancies having an occupant load of 10 or less are permitted to be equipped with a night latch, dead bolt, or security chain, provided such devices are openable from the inside without the use of a key or tool.

5. Delayed egress locks, installed and maintained in conformance with Section 1008.1.8.6.

6. Special egress-control devices installed and maintained in conformance with Section 1008.1.3.6.

7. In rooms, other than cells, where occupants are being restrained for safety or security reasons, special locking arrangements which comply with the requirements of Section 1008.1.10 are permitted.

Subp. 7.

IBC Section 1008.1.8.6.

IBC Section 1008.1.8.6 is amended to read as follows:

1008.1.8.6 Delayed egress locks. Approved, listed, delayed egress locks shall be permitted to be installed on doors serving any occupancy except Group A and H occupancies in buildings that are equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or an approved automatic smoke detection system installed in accordance with Section 907, provided that the doors unlock in accordance with Items 1 through 6 below. A building occupant shall not be required to pass through more than one door equipped with a delayed egress lock before entering an exit.

1. The doors unlock upon actuation of the automatic sprinkler system or automatic fire detection system.

2. The doors unlock upon loss of power controlling the lock or lock mechanism.

3. The door locks shall have the capability of being unlocked by a signal from the fire command center.

4. The initiation of an irreversible process which will release the latch in not more than 15 seconds when a force of not more than 15 pounds (67 N) is applied for one second to the release device. Initiation of the irreversible process shall activate an audible signal in the vicinity of the door. Once the door lock has been released by the application of force to the releasing device, relocking shall be by manual means only.

Exception: Where approved, a delay of not more than 30 seconds is permitted.

5. A sign shall be provided on the door located above and within 12 inches (305 mm) of the release device reading: PUSH UNTIL ALARM SOUNDS. DOOR CAN BE OPENED IN 15 [30] SECONDS.

6. Emergency lighting shall be provided at the door.

Subp. 8.

IBC Section 1008.1.

IBC Section 1008.1 is amended by adding subsections as follows:

1008.1.10 Special locking arrangements. Special locking arrangements meeting the requirements of Sections 1008.1.10 through 1008.1.10.5 are permitted for rooms, other than cells, where the occupants are being restrained for safety or security reasons. The use of Sections 1008.1.10 through 1008.1.10.5 may be revoked by the fire code official or building official for due cause.

1008.1.10.1 Locking hardware. Locking devices shall release upon any of the following conditions:

1. Activation of the automatic sprinkler system.

2. Activation of any automatic fire detection device.

3. Activation of any automatic fire alarm system.

4. Loss of electrical power to the locking device or the fire alarm system.

5. Activation of the fire alarm trouble signal.

6. Operation of a manual switch located in an approved location.

All locking devices shall be designed to fail in the open position following the release of the locking devices for any of the conditions specified above. Relocking of the devices shall be by manual means only at the door.

1008.1.10.2 Fire-extinguishing system. When special locking arrangements are used, the room or area being secured shall be protected with quick-response sprinklers.

1008.1.10.3 Fire alarm and detection. When special locking arrangements are used, the room or area and spaces between the room or area and an exterior exit door shall be protected with automatic smoke detection connected to the building's fire alarm system. If the walls of the room or area do not extend to the ceiling, automatic smoke detection can be provided in the adjacent room or area, provided that there are no substantial obstructions to delay activation of the smoke detection.

1008.1.10.4 Construction. Rooms or areas containing these special locking arrangements shall be constructed of noncombustible materials having a minimum one-hour fire-resistive construction. Doors separating the rooms from other spaces shall swing in the direction of egress travel from the room and have a fire-protection rating of not less than 20 minutes. Doors need not be self closing. The interior finish of the wall and ceiling surfaces must not exceed a Class C.

1008.1.10.5 Location. The room or rooms shall be located on a floor that provides direct grade-level access when located in buildings or portions thereof consisting of nonrated construction.