IBC section 403.4.8.3 is amended to read as follows:
403.4.8.3 Standby power loads. The following are classified as standby power loads:
1. power and lighting for the fire command center required by Section 403.4.6;
2. ventilation and automatic fire detection equipment for smokeproof enclosures; and
3. passenger elevators serving occupied floors more than 75 feet (22, 860 mm) above the lowest level of fire department vehicle access.